Yes, the calculation of the inverter's DC input
can be done following the provisions of the photovoltaic power station design
code "GB50797". This involves considering both the open circuit
voltage of the modules (determining the maximum number of components that can
be connected in each string) and the working voltage of the modules (taking
into account the MPPT efficiency of the inverter). The actual calculation can
be tailored based on the specific conditions and requirements of the
installation.
Components with different power ratings should
generally not be connected in series because their power ratings determine
their working currents, and when connected in series, the entire string will be
limited by the smallest component's current. However, in cases where the power
difference is relatively small, it might be possible to connect them in series.
The larger the power difference between the components, the greater the
difference in current, making it more challenging to achieve proper string operation.
It is recommended to avoid significant power differences when considering
series connections to ensure efficient and safe operation.
1. Generally,
once the power grid restores its normal operation, the inverter will
automatically reconnect to the grid. However, if the issue persists:
2. Verify
if the power grid is reliably supplying electricity.
3. Inspect
the AC wiring to ensure all connections are secure and properly tightened.
4. Double-check
that the AC cable is correctly connected to the appropriate terminal (ensuring
the live wire is not mistakenly connected to the neutral wire).
5. Confirm that the AC circuit breaker is closed
and functioning properly.
1. In general situations, once the power grid
returns to normal, the inverter will automatically reconnect to the grid.
However, if the problem persists:
2. Measure the actual voltage of the power grid
to confirm if it is indeed lower than the set value. If so, please contact the
local power company for a solution.
3. You can also use the App to check if the
protection parameter settings are according to the requirements.
4. Inspect the AC wiring to ensure all
connections are secure and properly tightened.
There are two possible situations:
During summer, the power generation of
photovoltaic power plants may not be as high as during clear spring or autumn
days, mainly due to the adverse impact of sustained high temperatures on the
components. As the temperature rises, the output power of the modules decreases,
leading to a reduction in power generation of approximately 0.44% for every
degree of temperature increase.
If the power station's components are oversized
in comparison to the inverter capacity, excessive output power may cause the
inverter to operate at a reduced capacity. To address this, it is essential to
check whether the inverter's output parameters fall within the normal range and
take preventive measures to avoid derating operations, which can result in
decreased power generation.
Typically,
the total power output of the solar panels can exceed the inverter's rated
capacity, as long as the voltage of each string remains below the inverter's
maximum system voltage. A 6KW inverter with 2 MPPTs can be configured with one
or two strings of solar panels, and in either case can produce up to or even
more than the rated power of 6KW.